Summary: EMC Directive 2014/30/EU divides the equipment it covers into two groups: apparatus and fixed installations. CE marking, the declaration of conformity and conformity assessment apply to apparatus; fixed installations follow good engineering practices instead.

The EMC Directive 2014/30/EU divides equipment within its scope into two groups: apparatus and fixed installations. The distinction is more than terminology; the obligations for CE marking, the declaration of conformity and conformity assessment are completely different for the two groups. It is the first question that companies building machine lines, energy facilities or industrial automation projects need to answer.

What Is Apparatus?

Electronic apparatus tested in a semi-anechoic EMC chamber

Apparatus means any finished appliance, or combination of appliances made available on the market as a single functional unit, intended for the end user and liable to generate electromagnetic disturbance or be affected by it. The Directive also treats the following as apparatus:

  • components or sub-assemblies intended to be incorporated into apparatus by the end user;
  • mobile installations: combinations of apparatus and other devices intended to be moved and operated in a range of locations.

What Is a Fixed Installation?

Fixed installation in a factory: electrical distribution panels and cable trays

A fixed installation is a particular combination of several types of apparatus and, where applicable, other devices, which are assembled, installed and intended to be used permanently at a predefined location. Industrial production plants, power plants, grid infrastructure and large building automation systems are typical examples.

How Do the Obligations Differ?

Topic Apparatus Fixed installation
Essential requirements (Annex I) Apply Apply
Conformity assessment procedure Annex II or Annex III Not applicable
EU declaration of conformity Mandatory None
CE marking Mandatory None
Documentation Technical documentation Records of good engineering practices
Responsible party Manufacturer Person responsible for the installation

A fixed installation is installed using good engineering practices and respecting the information on the intended use of its components. These practices are documented, and the documentation is kept by the responsible person at the disposal of the competent authorities for inspection for as long as the installation is in operation.

Apparatus Intended for a Specific Fixed Installation

For apparatus intended for incorporation into a given fixed installation and not otherwise made available on the market, conformity assessment, the declaration of conformity and CE marking are not mandatory. However, the accompanying documentation must state:

  • the fixed installation the apparatus is intended for and that installation’s electromagnetic compatibility characteristics;
  • the precautions to be taken when incorporating the apparatus so as not to compromise the conformity of the installation;
  • information identifying the apparatus and its manufacturer.

If the same apparatus is also sold as a catalogue product, it cannot benefit from this exception; the normal apparatus obligations apply.

Commonly Confused Cases

  • A single machine: Even if permanently installed in a factory, a machine placed on the market as a single functional unit is apparatus; EMC conformity assessment, a declaration and CE marking are required.
  • A production line assembled on site: A line built on site from machines of different manufacturers may be a fixed installation, but each machine forming the line is itself subject to the apparatus obligations.
  • Transportable systems: Systems intended to be moved, such as containerised generator sets or mobile substations, are mobile installations and follow the rules for apparatus.
  • CE-marked apparatus within an installation: CE marking of the individual components does not mean that the installation as a whole meets the essential requirements; installation and cabling practices are decisive.

If Problems Arise with a Fixed Installation

Where there are indications that a fixed installation does not comply, in particular following complaints about electromagnetic disturbance, the competent authorities may request evidence of compliance and, where appropriate, initiate an assessment. If non-compliance is found, measures to bring the installation into conformity with the essential requirements may be imposed.

TESTPLUS is a notified body (NB 2908) under Directive 2014/30/EU and carries out EMC conformity assessment. It is one of 7 bodies worldwide notified for all three directives on machinery, outdoor noise and EMC. For scope, see our Electromagnetic Compatibility (2014/30/EU) page.

Frequently Asked Questions

Does apparatus intended for a specific installation need CE marking?

Under Article 19 of 2014/30/EU, apparatus designed for incorporation into a given fixed installation and not otherwise made available on the market does not require an EU declaration of conformity or CE marking. The accompanying documentation must, however, identify the installation, its electromagnetic compatibility characteristics and the precautions to be taken during installation, together with the manufacturer’s name and address and information identifying the apparatus.

Is a declaration of conformity issued for a fixed installation?

No. No EU declaration of conformity is issued and no CE marking is affixed for fixed installations. The installation must be built according to good engineering practices, these practices must be documented, and the documents must be kept available to the competent authorities for as long as the installation is in operation. Responsibility lies with the person designated by national legislation, usually the operator of the installation or the contractor that built it. Apparatus added to the installation later must not compromise its EMC characteristics.